Search Catalog
      GO   
 All Categories    Fire Pump
All Categories > New Products > Fire Pump > Item # FPM2514T  

Item # FPM2514T, Baldor-Reliance 22.25 in. Overall Length and 90 Power Factor Fire Pump AC Motor


    border="0" Printable Page  
    Email Email This Page  
    Save To Favorites Save To Favorites
  

20/15HP,3460/2900RPM,3PH,60/50HZ,254T





Specifications

UPC Code

781568812976

Type

AC Motor

Mounting Type

Rigid Base

Frame Type

254T

Insulation Class

F

Brand

Baldor-Reliance

Agency Approvals

CSA, CSA EEV, UL, UR

Auxiliary Box

No Auxiliary Box

Auxiliary Box Lead Termination

None

Bearing Grease Type

POLYREX EM (-20 to +300 ºF)

Blower

None

Drip Cover

No Drip Cover

Duty Rating

Continuous

Electrically Isolated Bearing

Not Electrically Isolated

Feedback Device

No Feedback

Front Face Code

Standard

Front Shaft Indicator

None

Heater Indicator

No Heater

Inverter Code

Inverter Ready

Motor Lead Exit

KO Box

Motor Lead Termination

Flying Leads

Motor Standards

NEMA

Product Family

General Purpose

Pulley End Bearing Type

Ball Bearing

Pulley Face Code

Standard

Pulley Shaft Indicator

Standard

Rodent Screen

None

Shaft Extension Location

Pulley End

Shaft Ground Indicator

No Shaft Grounding

Starting Method

Wye Start - Delta Run

Thermal Device - Bearing

None

Thermal Device - Winding

None

Vibration Sensor Indicator

No Vibration Sensor

Frame Material

Steel

XP Class and Group

None

KVA Code

G

Lifting Lugs

Standard Lifting Lugs

Locked Bearing Indicator

No Locked Bearing

Motor Lead Quantity/Wire Size

12 at 12 AWG

Motor Type

3742M

Shaft Slinger Indicator

No Slinger

Speed Code

Single Speed

Winding Thermal 1

None

Winding Thermal 2

None

Design Code

B

RoHS Status

RoHS Compliant

Power Rating

15.000 hp
20.000
hp

Number of Phases

3

Number of Poles

2

Shaft Rotation

Reversible

Service Factor

1.15

Speed [Max]

3,450 rpm

Frequency

50 Hz
60
Hz

Ambient Temperature

40 ºC

High Voltage Full Load Amps

21.0 A

Speed

2,860 rpm
3,450
rpm

Efficiency at 100% Load

90.2 %

Power Factor

90

Voltage at 50 Hz

190 V
380
V

Voltage at 60 Hz

230 V
460
V

Current at 460 V Voltage

23.0 A

Current at 230 V Voltage

46.0 A

Current at 190 V Voltage

42.0 A

Current at 380 V Voltage

21.0 A